Items of Flow meter for compressed air and gases VA 500 with dispaly
Product | Description | Order No. |
VA 500 consumption probe in the basic version: standard (92.7 m/s), probe length 220 mm, without display | 0695 5001 | |
Display | Z695 5000 |
Special features volume flow measurement
- Including temperature measurement
- RS 485 interface, Modbus-RTU as standard
- Integrated display for m3/h and m3
- Applicable from 1/2" to DN 1000
- Easy installation under pressure
- 4...20 mA analogue output for m3/h or m3/min
- Pluse output for m3 or M-bus (optional)
- Inner diameter adjustable by means of keys
- Flow meter can be reset
- Adjustable by means of keypad on the display: Refrence conditions, °C and mbar, 4...20 mA scaling, pluse weight
Flow measuring ranges VA 500 for compressed air (ISO 1217: 1000 mbar, 20°C) | ||||||||
Inside diameter of pipe | VA 500 Standard (92.7 m/s) | VA 500 Max. (185.0 m/s) | VA 500 High-Speed (224.0 m/s) | |||||
Inch | mm | Measuring range full scale | Measuring range full scale | Measruting range full scale | ||||
m3/h | (cfm) | m3/h | (cfm) | m3/h | (cfm) | |||
1/2" | 16.1 | DN 15 | 759 l/min | 26 | 1516 l/min | 53 | 1836 l/min | 64 |
3/4" | 21.7 | DN 20 | 89 m3/h | 52 | 177 m3/h | 104 | 215 m3/h | 126 |
1" | 27.3 | DN 25 | 148 m3/h | 86 | 294 m3/h | 173 | 356 m3/h | 210 |
1 1/4" | 36.0 | DN 32 | 266 m3/h | 156 | 531 m3/h | 312 | 643 m3/h | 378 |
1 1/2" | 41.9 | DN 40 | 366 m3/h | 215 | 732 m3/h | 430 | 886 m3/h | 521 |
2" | 53.1 | DN 50 | 600 m3/h | 353 | 1197 m3/h | 704 | 1450 m3/h | 853 |
2 1/2" | 68.9 | DN 65 | 1028 m3/h | 604 | 2051 m3/h | 1207 | 2484 m3/h | 1461 |
3" | 80.9 | DN 80 | 1424 m3/h | 838 | 2842 m3/h | 1672 | 3441 m3/h | 2025 |
4" | 110.0 | DN 100 | 2644 m3/h | 1556 | 5278 m3/h | 3106 | 6391 m3/h | 3761 |
5" | 133.7 | DN 125 | 3912 m3/h | 2302 | 7808 m3/h | 4594 | 9453 m3/h | 5563 |
6" | 159.3 | DN 150 | 5560 m3/h | 3272 | 11096 m3/h | 6530 | 13436 m3/h | 7907 |
8" | 200.0 | DN 200 | 8785 m3/h | 5170 | 17533 m3/h | 10318 | 21229 m3/h | 12493 |
10" | 250.0 | DN 250 | 13744 m3/h | 8088 | 27428 m3/h | 16141 | 33211 m3/h | 19544 |
12" | 300.0 | DN 300 | 19814 m3/h | 11661 | 39544 m3/h | 23271 | 47880 m3/h | 28177 |
Comparison of Flow meter with display and without display
The main difference between a flow meter VA 500 with display and a flow meter VA 500 without display is the presence of a display screen on the device. The flow meter VA 500 with display will have a built-in screen that shows real-time flow rate readings, totalized flow volume, and possibly other relevant information. This makes it easier for the user to monitor and track the flow measurements directly on the device.On the other hand, the flow meter VA 500 without display will not have a built-in screen, so the user will need to connect it to an external display or monitoring system to view the flow rate and other data. This may require additional equipment and setup but can be a cost-effective option for applications where a separate display is already available.
In summary, the main difference is the presence or absence of a display screen on the flow meter itself, which affects how the flow data is displayed and accessed by the user.
Parameters | m3/h, l/min (1000 mbar, 20 °C) in case of compressed air or Nm3/h, Nl/min (1013 mbar, 0 °C) in case of gases |
Units adjustable via keys at display | m3/h, m3/min, l/min, l/s, ft/min, cfm, m/s, kg/h, kg/min, g/s, lb/min, lb/h |
Adjustable via keypad | Diameter for volume flow calculation, counter resettable |
Sensor | Thermal mass flow sensor |
Measured medium | Air, gases |
Gas types are adjustable over CS service software or CS data logger | Air, nitrogen, argon, helium, CO2, oxygen, vacuum |
Measuring range | See Measuring range table |
Accuracy (m.v: of meas. value) (f.s.: of full scale) | ±1.5% of m.v. ± 0.3% of f.s. on request: ±1% of m.v. ± 0.3% of f.s. |
Operating temperature | -30... 110°C sensor tube -20...+70°C housing |
Operating pressure | -1...50 bar (for pressure > 10 bar order additional high-pressure protection) |
Digital output | RS 485 interface, (Modbus-RTU), optional: Ethernet interface PoE, M-Bus |
Analogue output | 4...20 mA for m3/h or l/min |
Pluse output | 1 pulse per m3 or per litre electrically isolated. Pluse weight can be set on the display. Alternatively, the pluse output can be used as an alarm |
Supply | 18...36 VDC, 5 W |
Burden | < 500 Ω |
Housing | Polycarbonate (IP 65) |
Sensor tube | Stainless steel, 1.4301 Installation length 220 mm, Ø 10 mm |
Mounting thread | G 1/2", G 1/2" NPT male thread |
Ø housing | 65 mm |
Mounting position | any |