EXTENDED HEAT EXCHANGE
RFE dryers feature a very robust 2-in-1 aluminum heat exchanger with an air-to-air heat exchanger, the air-to-air heat exchanger with a water separator connected externally through Victaulic connections. This advanced heat exchanger has been specially designed to maximize the heat transfer coefficient. Oversized Demister separator ensures optimum dew point performance and guarantees industry-leading pressure drops.
Refrigeration dryer DRYBERG | DRYBERG®️ RF25/AC |
Volume flow (m3/h) at +3 °C | 1500 |
Power consumption (kW) | 2,80 |
Pressure loss (Δp bar [g]) | 0,08 |
Air connection (ø) | DN80-PN16 |
Dimensions AxBxC (mm) | 1465x790x1000 |
Weight (kg) | 265 |
In the case of divergent operating pressure: Divide volume flow by factor
bar (g) | 4 | 5 | 6 | 7 | 8 | 10 | 12 | 14 |
Correction factor | 0.77 | 0.86 | 0.93 | 1.00 | 1.05 | 1.14 | 1.21 | 1.27 |
°C | 25 | 30 | 35 | 40 | 45 | 50 |
Correction factor | 1.00 | 0.96 | 0.91 | 0.85 | 0.76 | 0.64 |
°C | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 |
Correction factor | 1.27 | 1.21 | 1.00 | 0.84 | 0.70 | 0.57 | 0.48 | 0.42 | Auf Anfrage |
°C | 3 | 5 | 7 | 10 |
Correction factor | 1.00 | 1.09 | 1.19 | 1.37 |
All articles in this group