Proper use
The manufacturer shall not be liable for problems occurring as a consequence of improper use. The user alone is responsible for any damage resulting from that.
Furthermore, the correct use includes the compliance with the installation instructions, in particular in respect of:
• The voltage and frequency of the main voltage supply.
• The pressure, temperature and flow rate of the inlet air.
• The pressure, temperature and cooling-water throughput (water-cooled).
• The ambient temperature.
When delivered, the dryer is tested and fully assembled. The customer only needs to connect the device to the system in accordance with the instructions in the following chapters.
Refrigeration dryer | DRYBERG®️ RF06/AC |
Volume flow (m3/h) at +3 °C | 366 |
Power consumption (kW) | 0,82 |
Pressure loss (Δp bar [g]) | 0,19 |
Air connection (ø) | G1 1/2" BSP-F |
Dimensions AxBxC (mm) | 885x555x580 |
Weight (kg) | 54 |
Operating pressures multiply air flow with correction factor f1
bar (g) | 4 | 5 | 6 | 7 | 8 | 10 | 12 | 14 |
f1 | 0.77 | 0.86 | 0.93 | 1.00 | 1.05 | 1.14 | 1.21 | 1.27 |
Ambient air temperatures multiply air flow with correction factor f2
°C | 25 | 30 | 35 | 40 | 45 |
f2 | 1.00 | 0.95 | 0.88 | 0.79 | 0.68 |
Compressed air inlet temperatures multiply air flow with correction factor f3
°C | 25 | 30 | 35 | 40 | 45 | 50 | 55 |
f3 | 1.20 | 1.11 | 1.00 | 0.81 | 0.67 | 0.55 | 0.45 |