Product information "DRYBERG®️ RF110/AC Refrigeration dryer "
Refrigeration dryer DRYBERG®️ RF110/AC equals to DRYPOINT®️ RA6600/AC
THERMAL STORAGE OPERATION FOR LOW AIR FLOWS
The refrigerant compressor cycles ON/OFF for maximum savings and reliability. Since the refrigeration capacity is greater than the load, the excess capacity cools the all-in-one exchanger that acts like a thermal storage.
• For high/medium flows, the dryer applies the Impulse Technology to regulate its drying capacity.
• For low air flows, the dryer utilizes the “thermal storage” operation.
In the case of divergent operating pressure: Divide volume flow by factor
In the case of divergent ambient temperature: Divide volume flow by factor
In the case of divergent inlet temperature: Divide volume flow by factor
In the case of divergent pressure dew point: Divide volume flow by factor
• For high/medium flows, the dryer applies the Impulse Technology to regulate its drying capacity.
• For low air flows, the dryer utilizes the “thermal storage” operation.
Technical Data of Refrigeration dryer DRYBERG® RF110/AC
Refrigeration dryer | DRYBERG®️ RF110/AC |
Volume flow (m3/h) at +3 °C | 6624 |
Power consumption (kW) | 10,80 |
Pressure loss (Δp bar [g]) | 0,26 |
Air connection (ø) | DN150-PN16 |
Dimensions AxBxC (mm) | 1810x1300x1750 |
Weight (kg) | 940 |
In the case of divergent operating pressure: Divide volume flow by factor
bar (g) | 4 | 5 | 6 | 7 | 8 | 10 | 12 | 14 |
Correction factor | 0.77 | 0.86 | 0.93 | 1.00 | 1.05 | 1.14 | 1.21 | 1.27 |
°C | 25 | 30 | 35 | 40 | 45 | 50 |
Correction factor | 1.00 | 0.96 | 0.91 | 0.85 | 0.76 | 0.64 |
°C | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 |
Correction factor | 1.27 | 1.21 | 1.00 | 0.84 | 0.70 | 0.57 | 0.48 | 0.42 | Auf Anfrage |
°C | 3 | 5 | 7 | 10 |
Correction factor | 1.00 | 1.09 | 1.19 | 1.37 |