Refrigeration dryer DRYBERG®️ RF16/AC equals to DRYPOINT®️ RA960/AC
Aluminium heat exchanger
The heat exchanger module consists of an air/air heat exchanger, an air/refrigerant heat exchanger, and of a high-performance separator. The compressed air flows top-down through the heat exchanger. The large cross-sections of the flow passages cause low flow rates and low compressed-air losses. In the air/air heat exchanger, the heat exchange is effected in a reverse current. This guarantees maximum heat transfer. The heat transfer in the air/refrigerant heat exchanger also takes place in a reverse current. This allows full evaporation of the refrigerant. The high-performance separator ensures almost complete separation of the condensate. Maintenance of the high-performance separator is not required.
Technical Data of Refrigeration dryer DRYBERG® RF16/AC equal to DRYPOINT® RA960/AC
Refrigeration dryer |
DRYBERG®️ RF16/AC |
Volume flow (m3/h) at +3 °C |
960 |
Power consumption (kW) |
1,73 |
Pressure loss (Δp bar [g]) |
0,15 |
Air connection (ø) |
G2 1/2 BSP-F |
Dimensions AxBxC (mm) |
1105x665x725 |
Weight (kg) |
161 |
In the case of divergent operating pressure: Divide volume flow by factor
bar (g) |
4 |
5 |
6 |
7 |
8 |
10 |
12 |
14 |
Correction factor |
0.77 |
0.86 |
0.93 |
1.00 |
1.05 |
1.14 |
1.21 |
1.27 |
In the case of divergent ambient temperature: Divide volume flow by factor
°C |
25 |
30 |
35 |
40 |
45 |
50 |
Correction factor |
1.00 |
0.96 |
0.91 |
0.85 |
0.76 |
0.64 |
In the case of divergent inlet temperature: Divide volume flow by factor
°C |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
Correction factor |
1.27 |
1.21 |
1.00 |
0.84 |
0.70 |
0.57 |
0.48 |
0.42 |
Auf Anfrage |
In the case of divergent pressure dew point: Divide volume flow by factor
°C |
3 |
5 |
7 |
10 |
Correction factor |
1.00 |
1.09 |
1.19 |
1.37 |
Downloads
Manual DRYBERG®️ RF/AC, PDF( Size: 5 MB )