Refrigeration dryer DRYBERG®️ RF13/AC equals to DRYPOINT®️ RA750/AC
Minimum installation requirements:
• Choose an area which is clean and dry, free from dust and protected against atmospheric disturbances.
• The load-bearing zone must be even, horizontal and able to bear the weight of the dryer.
• Minimum ambient temperature +1°C.
• Maximum ambient temperature +50°C.
• Ensure a proper cooling air replacement.
• Allow a sufficient clearance on each side of the dryer for proper ventilation and to facilitate maintenance operations. The dryer does not require attachment to the floor surface.
Technical Data of Refrigeration dryer DRYBERG® RF13/AC
Refrigeration dryer |
DRYBERG®️ RF13/AC |
Volume flow (m3/h) at +3 °C |
750 |
Power consumption (kW) |
1,45 |
Pressure loss (Δp bar [g]) |
0,07 |
Air connection (ø) |
G2 1/2 BSP-F |
Dimensions AxBxC (mm) |
1105x665x725 |
Weight (kg) |
141 |
In the case of divergent operating pressure: Divide volume flow by factor
bar (g) |
4 |
5 |
6 |
7 |
8 |
10 |
12 |
14 |
Correction factor |
0.77 |
0.86 |
0.93 |
1.00 |
1.05 |
1.14 |
1.21 |
1.27 |
In the case of divergent ambient temperature: Divide volume flow by factor
°C |
25 |
30 |
35 |
40 |
45 |
50 |
Correction factor |
1.00 |
0.96 |
0.91 |
0.85 |
0.76 |
0.64 |
In the case of divergent inlet temperature: Divide volume flow by factor
°C |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
65 |
70 |
Correction factor |
1.27 |
1.21 |
1.00 |
0.84 |
0.70 |
0.57 |
0.48 |
0.42 |
Auf Anfrage |
In the case of divergent pressure dew point: Divide volume flow by factor
°C |
3 |
5 |
7 |
10 |
Correction factor |
1.00 |
1.09 |
1.19 |
1.37 |
Downloads